- 20 I/O points (8DI + 8DO + 4AI, see the Specifications table down the page for details)
- Support for analog signals of type 4-20 mA or 0-10 V
- RS485 interface and Modbus RTU/ASCII (Master/Slave)
- Extended operation temperature range: -40…+55 ºС
- USB-powered in the programming mode
- Software-based features include: retain variables, day timer, week timer, PID control, etc.
- Compact enclosure (5x standard MCB = 90mm in width) suitable for installation into a domestic consumer unit as well as into any control cabinet
- Removable terminal blocks
- Convenient battery replacement
PR100 is a compact Mini-PLC designed to solve basic automation tasks in, for example, lighting control, pumping control, ventilation and heating control, and other simple control systems.
With its minimum width, which measures as narrow as five standard MCBs placed inline, and dedicated enclosure form, the PR100 Mini-PLC allows for space-saving installation even in smaller consumer units , not to mention control cabinets. This device can operate in non-heated environments down to -40°C as well as in heated ones in temperatures up to +55°C.
An application program is written in function block format in the akYtec ALP programming software available free of charge. The control algorithm is uploaded to the device memory through a micro USB cable.
Variants
PR100.24.2.1 | 24 V DC, 8DI + 8DO + 4AI, 1x RS485 (Modbus RTU/ASCII) |
General | |||||
---|---|---|---|---|---|
Power supply | 24 (9...30) V DC | ||||
Power consumption, max. | 4 W | ||||
Real Time Clock | Backup 5 years (CR2032) | ||||
Real Time Clock accuracy | ± 3 s/day | ||||
Extension modules | none | ||||
Programming | |||||
Programming environment | akYtec ALP | ||||
Programming language | FBD | ||||
Programming interface | Mini-USB | ||||
Memory | ROM | 128 kB | |||
RAM | 16 kB | ||||
Retain memory | 1 kB | ||||
Network variables | 128 Byte | ||||
Communication | |||||
Interface | RS485 | ||||
Protocols | Modbus RTU / ASCII (Master / Slave) | ||||
Baud rate | 9.6...115.2 kBit/s | ||||
Digital inputs | |||||
Quantity | 8 | ||||
Type | Switch contact | ||||
Logical states | 1 | 8.5...30 V DC (2...5 mA) | |||
0 | -3...+5 V DC (0...15 mA) | ||||
Galvanic isolation | in groups of 4 | ||||
Universal inputs | |||||
Quantity | 4 | ||||
Input signal | Analog / Digital | ||||
Galvanic isolation | none | ||||
Analog input | 4-20 mA, 0-10 V | ||||
Resolution ADC | 12 bit | ||||
Digital outputs | |||||
Quantity | 8 | ||||
Type | relay, NO | ||||
Galvanic isolation | individual | ||||
Switching capacity | AC | 5 A, 250 V (resistive load) | |||
DC | 3 A, 30 V | ||||
Minimum load current | 10 mA (at 5 V DC) | ||||
Environment | |||||
Ambient temperature | -40...+55 °C | ||||
Storage temperature | -25...+55 °C | ||||
Humidity | up to 80 % (at +25 °C, non-condencing) | ||||
IP Code | IP20 | ||||
Enclosure | |||||
Dimensions | 88 × 108 × 58 mm | ||||
Weight | approx. 250 g | ||||
Material | plastic |
- ePLAN
- STEP Model
Setup_akYtecALP_2.7.353 |
PR_driver_v1.0.0 |
PR_driver_v3.5.0(for Win10) |
PR100 |
|
ePLAN_PR100-24.2.1 (*.zip 27.8 mb)
|
|
STEP_PR100-24.2.1 (*.zip 9.0 mb)
|
- Difference between PNP and Relais Output?
- What is the maximum load capacity of the inputs and outputs?
- Can I use the PR devices to control and monitor the current of my PV system?
- Loss of data. Do you lose the ALP program when you change the battery?
- Compatibility with HMI? What does a HMI need to be working with the PR-devices?
- What happens to my variables when we have a power failure? Is the program persistent?
- Can the PR-Devices be used as a PID-Controller?
- Can I control a pumping System with the PR-devices?
- What steps do I have to take to calibrate the PR-devices when i have uncertanties in the measurement?
- How does the Modbus register work and why is it in hexadecimal? (3x0000 to 3xFFFF)